IPHost - Our Data Centers Information

IPHost - Our Data Centers Information
×

We Administrate our own Data Center in Chisinau, Moldova

Electrical Infrastructure

  • Total installed power of 200KW. Power is supplied from two independent generators of 2000KW each located at a distance of 100m from the data centre.
  • 2 Legrand modular UPS of 60KW each, providing electrical continuity for the server room.
  • UPS batteries provide a minimum of 10 minutes of autonomy before the generators start up.
  • 240KW power provided by the two electric generators. They start automatically within 12 seconds of the power being cut off.
  • The generators are equipped with a pre-heater to start quickly in cold weather.
  • The 200 litre tank provides 24 hours of generator autonomy. The generator can also be powered when it is switched on.
  • The technical condition of the generators is checked weekly and then they are put into operation for one hour without load. Once every three months the centre is supplied with 100% electricity by the electric generators to test the generators under load.
  • The generators are connected to the monitoring system to check oil temperature, fuel level in the tank.
genalb
genrosu

Infrastructure Climate control

  • 64KW cooling power.
  • To maintain the temperature of 24 degrees in the server room 4 air conditioners are used, 2 DAIKIN + 2 SAMSUNG, each with a cooling capacity of 16KW.
  • Cooling appliances are connected to the monitoring system for their real-time status.
  • We use an electrically efficient HOT AISLE air conditioning scenario. It involves closing the hot air aisle.

Technical Infrastructure

  • We use Inergen gas detection and extinguishing system.
  • The data centre is set up on a concrete floor, which supports loads of 5000kg/m2.
  • Our data centre provides a total capacity for 400 physical servers that can be expanded up to 1300 servers.
  • The 8 video cameras provide 100% video surveillance of the centre.

Internet infrastructure

  • The installed internet capacity in the data centre is 60Gbps.
  • We are connected with the following operators: Moldtelecom, Orange, StarNet, Cogent, RETN, Voxility, Hurricane Electric, RDS/DIGI.
  • We are also connected with 4 Internet Exchanges: MD-IX, KIVIX, InterLan, RoNIX.
  • We have optical fiber between Chisinau (IPHOST) and Bucharest (NXData2) which provides us with a speed of 20Gbps between these locations.
  • 300km of our own fibre optic installed underground and overhead in mun. Chisinau and this advantage allows us to offer our customers Internet services at the office or dark fiber with speed up to 10Gbps.
  • DDoS protection protects the data centre from attacks of up to 4Tbps.

Data Center in Romania

We contract colocation services in Bucharest from the neutral colocation center NXData2 where we colocate most of our servers and routers for interconnection with Tier I ISPs.

Data Center in United Kingdom

We contract colocation services in Bucharest from the neutral colocation center NXData2 where we colocate most of our servers and routers for interconnection with Tier I ISPs.